TP-6811 7/16 69Section 5 Troubleshooting
Status Message CheckDescription/ CommentsAction
Load Shed 5 Status Info [ Notice The digital output for LoadPriority5Shed
is active (contacts closed), indicating the
5th priority load shed (load management
device
[) has been activated.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
Load Shed 6 Status Info [ Notice The digital output for LoadPriority6Shed
is active (contacts closed), indicating the
6th priority load shed (load management
device
[) has been activated.
Remove loads as required.
Check building wiring for
proper load distribution.
Check engine fuel supply.
* Programmable Interface Module (PIM) required
[ Load management device required (LCM, load shed kit, or RXT with combined interface/ load management board).
Figure 5-4 Status Messages Displayed on the RDC2 Controller