DL205 User Manual, 5th Edition
1-12
Chapter 1: Getting Started
Step 5: Connect the Power Wiring
Connect the wires as shown. Observe all precautions
stated earlier in this manual. For details on
wiring see Chapter 2 Installation, Wiring, and
Specifications. When the wiring is complete, replace
the CPU and module covers. Do not apply power at
this time.
Step 6: Connect the Programmer
Either connect the programming cable connected to
a computer loaded with DirectSOFT Programming
Software or a D2-HPP Handheld Programmer
(comes with programming cable) to the top port of
the CPU.
Step 7: Switch On the System Power
Apply power to the system and ensure the PWR indicator on the CPU is on. If not, remove
power from the system, check all wiring and refer to the troubleshooting section in Chapter 9
for assistance.
Step 8: Enter the Program
Slide the switch on the CPU to the STOP position (D2-250–1, D2-260 and D2-262 CPUs)
and then back to the TERM position. This puts the CPU in the program mode and allows
access to the CPU program. Edit a DirectSOFT program using the relay ladder diagram below
and load it into the PLC. If using an HPP, the PGM indicator should be illuminated on the
HPP. Enter the following keystrokes on the HPP:
NOTE: It is not necessary for you to configure the I/O for this system since the DL205 CPUs automatically
examine any installed modules and establish the correct configuration.
After entering the example program put the CPU in the RUN mode with DirectSOFT or after
entering the program using the HPP, slide the switch from the TERM position to the RUN
position and back to TERM. The RUN indicator on the CPU will come on indicating the
CPU has entered the run mode. If not, repeat Step 8 ensuring the program is entered properly
or refer to the troubleshooting guide in Chapter 9.
During Run mode operation, the output status indicator “0” on the output module should
reflect the switch status. When the switch is on, the output should be on.
Ground
Line
Neutral
Y0
X0
END
STR
$
1
B
ENT
OUT
GX
2
C
ENT
Handheld Program Keystrokes