Terminal – menus [Medium Plus/Comfort Plus Electronics] 9
Alarm messages 9.16
Supplement to Operating Instructions 150000773_00_en
BiG Pack 1270, BiG Pack 1270 XC, BiG Pack 1290, BiG Pack 1290 HDP, BiG Pack 1290 HDP XC, BiG Pack
1290 XC, BiG Pack 890, BiG Pack 890 XC
87
Short circuit to supply voltage
BX001-692
1 Signal line 2 Earth line
If the voltage on the signal line is above the value range that is valid for the sensor, there is a
connection to another live line.
Possible cause: A supply line is connected to sensor supply line.
9.16.1.3 Error on the control units
FMI 0: The upper limit value was exceeded.
Error number Designation Icon
522322-0 Force measurement amplifier 2, channel 1
FMA2
522333-0 Force measurement amplifier 2, channel 2
FMI 1: The lower limit value was not reached.
Error number Designation Icon
522322-1 Force measurement amplifier 2, channel 1
FMA2
522333-1 Force measurement amplifier 2, channel 2
FMI 12: The logic in the control unit or in the component is defective.
Error number Designation Icon
520198-12 When writing to the EEPROM, an error has
been detected.
EEPROM
FMI 19: There is a network/CAN error.
Error number Designation Icon
520192-19 BusOff on CAN 1
KBT
520193-19 BusOff on CAN 2
520194-19 BusOff on CAN 3
520195-19 BusOff on CAN 4
522535-19 Timeout for the RMC control unit detected.
RMC