Fan does not start or operate
Blown fuses
Electricity turned off
Wrong voltage
Failure of one or two phases
Low voltage, excessive line drop or inadequate wire
size
Check fuses/circuit breakers
Check for switched off or disconnected
Check for correct power supply
Check for correct power supply
Check for correct wire size
Motor not correctly connected
Load inertia too large for motor
Motor protection unit or switch are stopping as
temperature are too high
Motor too small and overload protector has broken
circuit
Connect the motor according to the motor label
Change motor
Reduce temperatures, check and change insulation
class, increase motor rating
Change motor
Broken belts
Loose pulleys
Replace belt
Tighten pulley
Excessive air flow
Excessive rotational fan speed
Pressure resistance offered by the system lower than
the design value
Gas density higher than the design value
High power absorption
Air flow already rotating in the opposite direction to
the fan rotation direction
Backward curved impeller installed backwards
Faults in the motor windings
Motor power supply voltage lower than the value
indicated on the identification plate
Replace motor
Check with motor supplier
Forward curved or backward blade fan operating below
design pressures.
Oversized ductwork
Filter(s) left out
Access door are open
Face and by-pass dampers oriented so coil dampers
are open at same time by-pass dampers are open
Redesign ductwork
Add in filter(s)
Close access door
Calculated horsepower requirements based on light
gas (eg. High temperature) but actual gas is heavy
(eg. Cold start up)
Fan not selected at efficient point of rating