GENERAL
WG1605-G-E3,WG1605-L-E3,WG1605-GL-E3, WSM
G-16
Checking Radiator Hoses and Clamp Bands
1. Check to see if the radiator hoses are properly fixed every 200
hours of operation or every six months, whichever comes first.
2. If the clamp is loose, apply oil to the threads and retighten it
securely.
3. The coolant hose is made of rubber and tends to age. It must be
replaced every two years. Also replace the clamp and tighten it
securely.
9Y1210571GEG0039US0
[6] CHECK POINTS OF EVERY 1000 HOURS
Checking PCV Valve
1. Disconnect the breather hose (3) from the intake manifold (1).
2. Blow into the breather hose (3).
3. Stop to blow.
4. Make sure that a slight operation sound is heard from the PCV
valve.
5. If there is no operation sound, replace the PCV valve (2).
6. Connect the breather hose (3) to the intake manifold (1)
9Y1210661GEG0039US0
Checking Coolant Hose of LPG / Natural Gas Vaporizer
1. Check the coolant hoses (1) for damage.
2. If the coolant hose is damaged, replace it.
9Y1210661GEG0019US0
Checking LPG / Natural Gas Lock Off Valve
1. Start the engine.
2. Make sure that an operation sound of solenoid is heard from the
LPG / natural gas lock off valve.
3. Make sure that there is no fuel leakage from the LPG / natural
gas lock off valve.
4. If there is no operation sound or fuel leakage, replace the LPG
/ natural gas lock off valve.
9Y1210661GEG0040US0
(1) Upper Hose (2) Lower Hose
(1) Intake Manifold
(2) PCV Valve
(3) Breather Hose
(1) Coolant Hose (2) LPG / Natural Gas Tank