5.1 Important Preliminary Checks KEW6310
5.1 KEW6310
5. Wining Configurations
5.1 Important preliminary checks
DANGER
Do not make measurements on a circuit in which electrical potential exceeds AC600V.
Connect the Power cord to a socket outlet. Never connect it to the socket outlet of AC240V or more.
The Clamp sensor, Voltage test leads and Power cord are to be connected to the instrument first.
The Voltage test leads or Clamp sensors should not be connected to the input terminals of the instrument
if not required for measurement.
The instrument should always be connected on the downstream side of a circuit breaker, which is safer
than the upstream side.
Do not open-circuit the secondary side of a supplementary CT while it is energized because of the high
voltage generated at the secondary side terminals.
Be careful to avoid short-circuiting the power line with the un-insulated part of the voltage test probes
during the setting up of the instrument. Transformer jaw tips are designed in such a way to avoid
short-circuiting. If the circuit under test has exposed conductive parts, extra care should be taken to
minimize the possibility of shorting.
WARNING
To avoid possible electric shock and short-circuit, always turn off the line under test when setting up the
instrument.
Do not touch the un-insulated tip of Voltage test probes. The use of safety insulted gloves is recommended.
Direction for correct measurements
Proper setting of wiring configuration should be made.
Ensure that the arrow mark on the clamp sensor points towards to load side.
* Reverse clamping switches the symbols (+/-) for active power [P].
Arrow mark: Points
towards load side.
Load
Source