6 Operating Control and Displays
6.3.2.1 Offline Mode
In OFFLINE mode, there is no permanent connection to BT300 (no parameter setting possi-
ble). OFFLINE mode is used simply as a display option for data. This allows to display previ-
ously stored data sets of end devices. No data set is loaded during start-up. The software
starts up with empty parameters.
Fig. 6-15 The setting online window
6.3.2.2 Online Mode
In ONLINE mode the end device is synchronised. The data of the end device are read out
completely. The permanent connection to the end device is monitored from both sides with a
time-out. While establishing connection to the device all functions are locked.
6.3.2.3 Connecting the BT 300 with the PC
If no LCM100 is connected to BT300:
1. Connect RAST 2,5 plug of the LSA100 into socket X31 of the BT300.
2. Connect SUB D 9 plug with USB/CAN converter.
3. Connect USB/CAN converter via USB to the PC.
If LCM100 is already connected to BT300:
1. Connect USB/CAN converter directly with SUB D 9 plug for LSB to LCM100.
2. Connect USB/CAN converter via USB to the PC.
Call up the LSB Remote Software
1. Select the path C:\ Programme\Lamtec.
2. Double-click LSBRemote.exe
The initial screen opens.