167
8 Options
No. Device Description Attribute
0040 BT300 Operating mode of firing rate controller
Operating mode of firing rate controller
0 = OFF
1 = constant control
2 = controlled by atmospheric conditions/external setpoint shift
3 = external firing rate (software version BT300 v 3.3 and LCM100 v1.4 and higher)
Group: 20
Min.: 0
Max.: 3
Default: 0
Write: 1/UI
Version: 1.0.0.0
0048 BT300 Controller setpoint 1 (for constant control/minimum value for control by atmospheric
condition) [°C] [bar]
Controller setpoint 1 minimum
Setting the setpoint minimum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 0.
If the firing rate controller is configured as a constant controller, setpoint 1 is set here.
Group: 20
Min.: 0
Max.: 999
Default: 75
Write: 0/UI
Version: 1.0.0.0
0049 BT300 Controller setpoint 1 maximum value (only for control by atmospheric conditions) [°C]
[bar]
Controller setpoint 1 maximum
Enter the setpoint maximum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 0.
If the burner firing rate controller is set to constant control, this parameter is not active.
Group: 20
Min.: 0
Max.: 999
Default: 75
Write: 0/UI
Version: 1.0.0.0
0050 BT300 Controller setpoint 2 (constant control/minimum value for control by atmospheric con-
ditions) [°C] [bar]
Controller setpoint 2 minimum
Enter the setpoint minimum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 1.
If the firing rate controller is configured as a constant controller, setpoint 2 is set here.
Group: 20
Min.: 0
Max.: 999
Default: 60
Write: 0/UI
Version: 1.0.0.0
0051 BT300 Controller setpoint 2 maximum value (only for control by atmospheric conditions) [°C]
[bar]
Controller setpoint 2 maximum value
Enter the setpoint minimum for the controller controlled by atmospheric conditions in
°C or bar.
The setting is active if the input ’Setpoint changeover’ = 1.
If the burner firing rate controller is set to constant control, this parameter is not active.
Group: 20
Min.: 0
Max.: 999
Default: 60
Write: 0/UI
Version: 1.0.0.0
0052 BT300 Firing rate controller: Lower limit [°C] [digit]