183
8 Options
8.1.16 Technical data LCM100
Fig. 8-24 Dimensions LCM100
General data
Power supply 90 - 250 V 47 - 63 Hz
Power consumption 18,2 VA
Housing Polyamide 6.6 (panel: polycarbonate)
Dimensions (HxWxD) 65x70x80 mm (2.56"x2.76"x3.15" in)
Weight 270 g (0.60 lb)
Flammability UL-94 V0 (panel: UL-94 V2)
Mounting position as desired
Installation TS35 mounting rail as per EN 50022
Connection cross section 2.5 mm
2
(13 AWG) (plugged LSB terminals: 0.5mm²/20 AWG)
24 VDC Output
Rated voltage 24 VDC +/-5% (SELV)
Output current max. 400 mA
Short-circuit resistant yes, unlimited
Input outside temperature
Valid sensors Pt100 or Pt1000 (switchable)
Range of measuring Outside temperature: -50 … +150 °C (-58 ... + 302°F)
Boiler temperature: 0 ... +400 °C (+32 ... + 752 °F)
Flue gas: 0 ... +400 °C (+32 ... + 752 °F)
Resolution 0,1 °C (32.18 °F)
Accuracy of measurement: Range -5 ... +150 °C = 1 °C (+23 ... +302 °F = ±33.8 °F)
Range +150 ... +400 °C = 2 °C (+302 ...+ 752 °F = ± 35.6 °F)
Constant data of low-pass filter
of first order:
2 s
Sampling rate: 32 Hz