201
8 Options
NOTICE
The limits of the technical data must be strictly adhered to.
8.3 Variable Speed Drive Module VSM100
The VSM100 is enhancing BT300 with an analogue output for a speed-controlled compressor
including its speed measurement.
NOTICE
Use VSM and DFM only with BT300 software version 3.0.0.0 or higher. Software versionens
before 3.0.0.0 do not support all necessary safety functions.
Connect the RPM module VSM100 via LSB (LAMTEC SYSTEM BUS) to BT300.
To insulate LSB from potential power supply voltage of BT300 a LCM100 or a LEM with power
supply 24 VDC SELV is needed. This is provided by DFM with 24 VDC via LSB.
Configure VSM100 by DIP switch.
The ramp speed for deceleration and acceleration ramps of the frequency inverter must not
be less than 10 s.
NOTICE
Before attaching VSM100 a valid curve including activated VSM mus be programmed.
NOTICE
Before you can use the device you must set the parameters P0403 ... P0406 in the BT300.
Dimensions (HxWxD) 80x70x65 mm (3.15"x2.76"x2.56" in)
Weight 265 g (0.58 lb)
Flammability UL-94 V0 (Panel: UL-94 V2)
Cable length refer to inputs/outputs of DFM300
Connection cross section 2,5 mm
2
(13 AWG)
Rast5-Module
Environmental conditions
Operation Climatic conditions Class 3K5 according to DIN EN 60721-3
Mechanic conditions Class 3M5 according to DIN EN 60721-3
Temperature range -15 ... +50 °C (+5 ... +122 °F)
(condensation is prohibited)
Transport Climatic conditions Class 2K3 according to DIN EN 60721-3
Mechanic conditions Class 2M2 according to DIN EN 60721-3
Temperature range -15 ... +50 °C (+5 ... +122 °F)
(condensation is prohibited)
Storage Climatic conditions Class 1K3 according to DIN EN 60721-3
Mechanic conditions Class 1M2 according to DIN EN 60721-3
Temperature range -15 ... +50 °C (+5 ... +122 °F)
(condensation is prohibited)
Electronic safety Protection class (DIN EN 60529) IP20