NOTICE
The limits of the technical data must be strictly adhered to.
8.4 Expansion Module for LSB - LEM100
The LEM100 adds an LSB interface (CAN) to BurnerTronic. The LEM100 isolates electrically
the BT-output and the connected modules.
You must connect 24 V protective low voltage externally to the LEM and the connected mod-
ules.
If you want to connect the BurnerTronic to LSB the LEM100 is required.
If you are running BurnerTronic in combination with LCM100 already, you do not need
LEM100, because LCM100 has a LSB interface and a 24-V-power-supply integrated.
8.4.1 DIP Switch
You can configure settings of LEM100 using DIP switches.
Functions of DIP switches
You can activate or deactivate the LSB terminating resistor by DIP switch 1.
DIP switches 2-3 are reserved.
Input pulse width min. 200 µs
Digital speed feedback input
Environmental Conditions
Operation Climatic conditions Class 3K5 according to DIN EN 60721-3
Mechanic conditions Class 3M5 according to DIN EN 60721-3
Temperature range -20 ... +60 °C (-4 ... +140 °F)
(condensation is prohibited)
Transport Climatic conditions Class 2K3 according to DIN EN 60721-3
Mechanic conditions Class 2M2 according to DIN EN 60721-3
Temperature range -20 ... +70 °C (-4 ... +158 °F)
(condensation is prohibited)
Storage Climatic conditions Class 1K3 according to DIN EN 60721-3
Mechanic conditions Class 1M2 according to DIN EN 60721-3
Temperature range -20 ... +70 °C (-4 ... +158 °F)
(condensation is prohibited)
Electronic safety Degree of protection (DIN EN60529) IP40 housing
IP20 terminals
DIP switch 1
1 CAN-Bus activated
0 CAN-Bus deactivated