8 Options
8.5.1.4 PROFIBUS DP Communication
While PBM is connected to PROFIBUS MASTER in active way, following messages were sent
to LSB:
Byte position Description Note
0 - 1 Operating mode Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern Operat-
ing Mode’
2 - 3 Fault code Fault codes refer to ’Error Codes BT300’ (DLT1205)
4 - 5 Internal firing rate Value 0 to 999
6 - 7 Status of digital inputs Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern Digital
Inputs’
8 - 9 Active curve set Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern curve
set’
10 - 11 Outputs, actual curve sets Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern Digital
Outputs’
12 - 13 Setpoint value O
2
Value 0 to 250 0,0 % to 25,0 %
14 - 15 Operating mode O
2
controller v 3.0 and higher:
Byte 15 active curve set
Byte 14 condition corresponding to 8.5.3 Appendix, table ’Bit Pattern
Operating mode O Controller’
16 - 17 Error information O
2
controller v. 3.0 and higher: Bit pattern corresponding to 8.5.3 Appendix, table
’Bit Pattern Failure Cause O Controller’
18 - 19 Actual value O
2
Actual value O
2
in steps of 0,01 %
20 - 21 Status of actual value O
2
Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern Status of
Actual Value O’
22 - 23 Correction value 1 v3.0 and higher: correction value
24 - 25 Quantity of fuel - oil Invalid values in current PBM version
26 - 27 Quantity of fuel - gas Invalid values in current PBM version
28 - 33 Reserved
34 - 35 Setpoint value boiler temperature/
steam pressure
16 bit integer
36 - 37 Actual value boiler temperature/
steam pressure
16 bit integer
38 - 39 Operating mode CO controller v3.0 and higher: Bit pattern corresponding to 8.5.3 Appendix, table ’Bit
Pattern Operating Mode CO Controller’
40 - 41 Error information CO controller v3.0 and higher: Bit pattern corresponding to 8.5.3 Appendix, table ’Bit
Pattern Failure Cause CO Controller’
42 - 43 Actual value CO 16 Bit integer
44 - 45 Status of actual value CO Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern Status of
Actual Value CO’
46 - 47 Flue gas temperature 16 bit integer in 0,1 °C
48 - 49 Status of flue gas temperature
Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern
Status of Flue Gas Temperature and Efficiency’
50 - 51 Efficiency 0 to 999 in steps of 0,1-%