216
8 Options
Tab. 8-1 specification of client input data
The assignment of Packet Data Units of Input data, transferred via PBM from PROFIBUS to
LSB:
52 - 53 Status of efficiency Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern Status of
Flue Gas Temperature and Efficiency’
54 - 55 Flame intensity 0 to 100 in steps of 1 %
56 - 57 Actual value monitoring output 16 bit Integer
58 - 59 Burner control state Bit pattern corresponding to 8.5.3 Appendix, table ’Bit Pattern FAT Sta-
tus’
Byte position Description Note
Byte position Description
0 - 1 Burner ON (byte 1, bit 0, 1: ON),
Fuel pre-selection (byte 1, bit 1, 1: oil, 0: gas), Fault reset (byte 1, bit 2)
2 - 3 Pre-setting burner firing rate, 0 ... 999,
Validation bit 15 = 1 (Byte 2, 3 = b1XXXXXXX XXXXXXXX):
Sets priority for burner firing rate pre-setting by PROFIBUS
4 - 5 pre-setting status of burner firing rate (actually not in use)
6 - 7 Pre-setting setpoint of burner firing rate controller,
0 ... 999, values correspond to the indication of actual value and setpoint value
8 - 9
Status of burner firing rate controller’s setpoint,
Validation bit 15 = 1 (Byte 8, 9 = b1XXXXXXX XXXXXXXX):
Evaluation of setpoint value by LCM
10 - 11 Smooth setpoint shift of firing rate controller, int16,
value range is defined by upper and lower limits.
12 - 13
Status of smooth setpoint shift of burner firing rate controller
Validation bit 15 = 1 (Byte 12, 13 = b1XXXXXXX XXXXXXXX):
sets analysis of setpoint shift by LCM