8.5.1.5 Technical Data PBM100
Fig. 8-46 Dimensions PBM100
NOTICE
The limits of the technical data must be strictly adhered to.
PBM100
Power supply 24 VDC +10/-15% via bus terminals
Current consumption 100 mA
Housing PA6.6 UL94-V0
Cover: Polycarbonate, transparent
Installation Support rail TH35 according to EN 60715
Dimensions (HxWxD) 72x51x70 mm (2.83"x2.01"x2.76" in)
Weight 105 g (0.23 lb)
Flammability UL-94 V0 (panel: UL-94 V2)
Lengths of cable Supply 24 VDC <10 m (32.81 ft)
LSB: max. 100 m (328.08 ft) (screened)
PROFIBUS DP: 100 m (328.08 ft) (screened)
Environmental conditions
Operation: Climatic condition class 3K5 as per DIN EN 60721-3
Mechanical condition class 3M5 as per DIN EN 60721-3
Temperature range -20 ... +60 °C (-4 °F ... +140 °F)
(condensation not permitted)
Transport: Climatic condition class 2K3 as per DIN EN 60721-3
Mechanical condition class 2M2 as per DIN EN 60721-3
Temperature range -20 ... +70 °C (-4 °F ... +158 °F)
(condensation not permitted)
Storage: Climatic condition Class 1K3 as per DIN EN 60721-3
Mechanical condition Class 1M2 as per DIN EN 60721-3
Temperature range -20 ... +70 °C (-4 °F ... +158 °F)
(condensation not permitted)
Protection class: according to DIN EN60529 IP40 (housing)
IP20 terminals