8 Options
8.5.2.5 Ethernet Communication
Sending Data on the Modbus/TCP (Master-Input-Data)
In the table below input data are specified, which BT300 transfers to the master (Modbus/TCP
–Client):
Register
1
Description Configuration
1 Operating mode Encoding see table in chapter 8.5.4.2 Bit Encoding: Operating
Mode
2 Fault code Fault codes see the fault code list BT300 (DLT1205)
3 Internal firing rate Value in 0,1 % (unsigned), Range: 0 ... 999
4 Condition of the digital inputs Encoding see table in chapter 8.5.4.3 Bit Encoding: Digital Inputs
5 Active curve set Encoding see table in chapter 8.5.4.4 Bit Encoding: Curve Set
6 Condition of the digital outputs Encoding see table in chapter 8.5.4.5 Bit Encoding: Digital Out-
puts
7O
2
Setpoint value Range: 0 ... 250 (unsigned) 0,0 % ... 25,0 %
8O
2
Trim operating mode Version 3.0 and higher:
Byte 15 active curve set
Byte 14 encoding see table in chapter 8.5.4.6 Coding: O
2
Control-
ler Operating Mode
9O
2
Trim fault condition Version. 3.0 and higher: Encoding see table in chapter 8.5.4.8 Bit
Encoding: Cause of Faults of O
2
Trim
10 O
2
Actual value O
2
Actual Value in steps of 0,01 % (unsigned)
11 Status of O
2
actual value Encoding see table in chapter 8.5.4.10 Bit Encoding: State of
Actual Value of CO
12 Optimisation value 1 Value in 0,1 % (unsigned), Range: 0 ... 999
Version 3.0 and higher: Optimisation value
13 Fuel meter 1 in ticks
14 Fuel meter 1 in ticks
15 - 17 reserved
18 Firing rate controller setpoint value The unit is depending on the parameter settings of the burner
control.
19 Firing rate controller actual value The unit is depending on the parameter settings of the burner
control.
20 CO Controller operating mode Version 3.0 and higher: Encoding see table in chapter 8.5.4.9 Bit
Encoding: Operating Mode of CO Controller
21 CO Controller cause of fault Version 3.0 and higher: Encoding see table in chapter 8.5.4.11 Bit
Encoding: Cause of Fault of CO Controller
22 CO Actual value Value in 0,01% (unsigned)
23 Status of CO actual value Encoding see table in chapter 8.5.4.10 Bit Encoding: State of
Actual Value of CO
24 Flue gas temperature Value in 0,1 °C
25 Status of flue gas temperature Encoding see table in chapter 8.5.4.12 Bit Encoding: State of Flue
Gas Temperature and Efficiency
26 Efficiency Range: 0 ... 999 in steps of 0,1 %
27 Status of efficiency Encoding see table in chapter 8.5.4.12 Bit Encoding: State of Flue
Gas Temperature and Efficiency
28 Flame intensity Range: 0 ... 100 in steps of 1 %
29 Current monitor output Range: 0... 1000 unsigned
30 Status of burner control Encoding see table in chapter 8.5.4.14 Encoding FAT State