226
8 Options
8.5.2.6 Technical Data EBM100
Fig. 8-47 Dimensions EBM100
NOTICE
The limits of the technical data must be strictly adhered to.
EBM100
Power Supply 24 VDC +10/-15% (SELV)
Current consumption 200 mA
Housing PA6.6 UL94-V0
Panel: Polycarbonate, transparent
Mounting Mounting rail TH35 according to EN 60715
Dimensions (HxWxD) 65x70x50 mm (2.56"x2.76"x1.97" in)
Weight 120 g (0.26 lb)
Flammability UL-94 V0 (panel: UL-94 V2)
Cable length Supply 24 VDC <10 m (32.81 ft)
Ethernet: according to Ethernet standards
Connection cross section Ethernet: RJ45 plug-in connection according to Ethernet standards
Environmental Conditions
Operation Climatic conditions Class 3K5 according to DIN EN 60721-3
Mechanic conditions Class 3M5 according to DIN EN 60721-3
Temperature range -20 ... +50 °C (-4 ... +122 °F)
(condensation is prohibited)
Transport Climatic conditions Class 2K3 according to DIN EN 60721-3
Mechanic conditions Class 2M2 according to DIN EN 60721-3
Temperature range -20 ... +70 °C (-4 ... +158 °F)
(condensation is prohibited)
Storage Climatic conditions Class 1K3 according to DIN EN 60721-3
Mechanic conditions Class 1M2 according to DIN EN 60721-3
Temperature range -20 ... +70 °C (-4 ... +158 °F)
(condensation is prohibited)
Degree of protection according to (DIN EN60529) IP40 housing
IP20 terminals