8 Options
Tab. 8-7 Status
Warnings
Tab. 8-8 Warnings
Faults
Tab. 8-9 Fault
Life Code Data
1 Device start
2 Initialisation CAN/LSB
3 Initialisation - detecting the burner control.
4 Initialisation - the fieldbus type is determined by the firmware of the protocol IC.
5 Operation
Status Description
Status Description
0 No warning is active.
1CAN failure
2 Failure on LSB? No LSB message received for more than 3 s.
3 Communication with the internal protocol IC is disrupted (Ethernet side).
4 Network configuration warning - irrelevant for PROFINET-IO
Status Description
0 Without fault
1CAN fault
2 Communication fault at the internal protocol IC.
3 A fault occurs in the communication with the internal protocol IC (Ethernet side).
4 The firmware of the internal protocol IC cannot be read or is not valid.
5 Several different burner controls are active in the same LSB family.
6 The parameter queries were not successful - not relevant for PROFINET-IO.
7 Internal fault
– A restart is not possible
– Replace the device
Device Type LSB Family Bit 6 ... Bit 7
1
Device Type or Group Byte 2
Burner control CMS 0 ... 3 23
ETAMATIC 0 ... 3 1
FMS/VMS 0 ... 3 1
BT300/BC300 0 ... 3 20 BT300
22 BC300
Lambda Transmitter LT1/LT2/LT3/LT3-F 0 ... 3 30 (LT1)
31 (LT10E)
32 (LT10P)
40 (LT2)
41 (LT3)
42 (LT3-F)