234
8 Options
8.5.4.4 Bit Encoding: Curve Set
Tab. 8-13 Encoding of curve sets
Tab. 8-14 Encoding curve sets
NOTICE
The number of available curve sets depends on the device type and configuration.
8.5.4.5 Bit Encoding: Digital Outputs
Tab. 8-15 Bit encoding of the digital outputs BT300/BC300
Curve set Byte 8 (Bit encoding) Byte 9
(value)
1 0000 0001 0
2 0000 0010 1
Curve set Byte 8 (Bit Encoding) Byte 9 (Value)
1 0000 0001 0
2 0000 0010 1
3 0000 0100 2
4 0000 1000 3
5 0001 0000 4
6 0010 0000 5
7 0100 0000 6
8 1000 0000 7
BT300 Bit Pattern HEX Code
Valve 1 curve set 1 XXXX XXXX XXXX XXX1 0x0001
Pilot valve XXXX XXXX XXXX XX1X 0x0002
Valve 2 curve set 2 XXXX XXXX XXXX X1XX 0x0004
Oil pump XXXX XXXX XXXX 1XXX 0x0008
Valve 1 curve set 2 XXXX XXXX XXX1 XXXX 0x0010
Spark igniter XXXX XXXX XX1X XXXX 0x0020
Valve 2 curve set 2 XXXX XXXX X1XX XXXX 0x0040
Fault (inverse) XXXX XXXX 1XXX XXXX 0x0080
Fan ON XXXX XXX1 XXXX XXXX 0x0100
Not assigned XXXX XX1X XXXX XXXX 0x0200
Oil valve 3 XXXX X1XX XXXX XXXX 0x0400
Fuel selection XXXX 1XXX XXXX XXXX 0x0800
Not assigned XXX1 XXXX XXXX XXXX 0x1000
Not assigned XX1X XXXX XXXX XXXX 0x2000
Not assigned X1XX XXXX XXXX XXXX 0x4000
Not assigned 1XXX XXXX XXXX XXXX 0x8000