EasyManua.ls Logo

Lamtec BT300 BurnerTronic - Page 57

Lamtec BT300 BurnerTronic
254 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
4 Design and Functions
p
1
V
1
= p
2
V
2
p = absolute pressure
V = gas volume
This is valid for the test of valve 1 V1:
Should t3 be negative, at least 1s must be set.
If the calculation of t3 for valve 2 is higher than t3 for valve 1, the value for the calculation of
valve 2 must be adjusted.
NOTICE
p
Schalt
must always be higher than p
out.
Otherwise V1 would be recognised as leaking even if it is not.
This is valid for the test of valve 2 V2:
If t3 is negative, at least 1 s must be set.
If the calculated t3 value of valve 1 is higher than t3 for valve 2, the calculated value of valve
1 must be adjusted.
Q
leak
Leakage rate in l/h
p
sw
Absolute pressure on the switching point of pressure monitor (adjusted over-
pressure + atmosphere pressure)
p
sw e
Adjusted overpressure on switching point of pressure monitor
p
out e
Output pressure on gas valve V2 during purge
p
Atm
Atmospheric pressure (average of 101,3 kPa at sea level)
V
test
Test volume between the valves
t2 Settling time is always 2 s
t3 Adjusted leakage check time
Q
leak
Leakage rate in l/h
p
sw
Absolute pressure on switching point of pressure monitor (adjusted overpres-
sure + atmosphere pressure)
p
sw e
Adjusted overpressure on the switching point of pressure monitor
p
in
Absolute input pressure on gas valve V1
p
in e
Overpressure at gas valve V1 input
p
Atm
Atmosphere pressure (average of 101,3 kPa at sea level)
V
test
Test volume between the valves
t2 Settling time is always 2 s
t3 Adjusted leakage check time

Table of Contents

Related product manuals