6 Operating Control and Displays
NOTICE
The actuators are running to the new position immediately after the modification.
To adjust channel 4 the fan motor must be running. The feedback setpoint curve of channel 4
must rise continuously.
NOTICE
The following firing rate points are available:
Ignition point , 200, 250, 300, 400, 500, 600, 700, 800, 900, 999
6.1.7.5 Deleting Curves
Delete firing-rate curve
6.1.7.6 Adjusting Controller
Pressing key BACK for longer than 2 s in menu ’Curve settings of the actuators’
causes a fault shut down.
Pressing key BACK after finishing the curve settings leads back to menu Settings’
Pressing key BACK during changing the firing rate discards the modification.
PID controller settings CO/O
2
controller settings O
2
trim settings
CO controller settings Si-CarboSen settings