4.3 PARAMETERS SETTING
The setting function is controlled by 3 buttons (Enter , Off ▲, On ▼): Enter ---goes into
the setting page and value adjustment; Off ▲ & On ▼---for choosing different pages.
After the UPS turn ON, press buttons & ▲ for 3 seconds and then goes into the setting
interface page. After finishing setting the parameter, press “ON” until exiting out of the
current interface.
Note: Figure at left corner is the page number of the setting pages. After entering the set-
ting interface, it will exit when without operation in 30s.
4.3.1 Mode setting
4.3.2 Output voltage class setting
Mode setting (Note: Inside the broken line is the flashing
part.)
After entering the setting menu, it’s mode setting de-
faulted, and the mode setting line flashing as in above
picture.
• Use button Enter to choose different mode. There
are 3 different modes for setting: ECO, NOR, CF.
• Press▲ or ▼ to exit the mode setting (save the
mode setting) and goes to output voltage setting or
Battery Test setting.
When under the mode setting press On▼ or when under
frequency setting press Off▲, it goes to the output vol-
tage setting. The output voltage line flashes as in above
picture.
• Use button Enter to choose the different output
voltage. There are 4 different voltages---208,220,
230, 240.
• Press▲ or ▼ to exit the output voltage setting (save
the output voltage setting) and goes to mode setting
or frequency setting.
Note: When powered by inverter, it is necessary to turn
off the inverter before setting voltage and frequency
level.
Mode setting (Note: Inside the broken line is the flashing part.)
Output voltage setting
(Note: Inside the broken line is the
flashing part.)