17
4.3.3 Output frequency class setting
4.3.4 Battery capacity setting
When under the output voltage setting press On or
when under battery capacity setting press Off, it goes
to the frequency setting. The frequency line flashes as in
above picture.
Use button Enter to choose the different frequen-
cy. There are 2 different frequency---50/60Hz.
Press or to exit the frequency setting (save
the frequency setting) and goes to output voltage
setting or battery capacity setting.
Note: When powered by inverter, it is necessary to turn
off the inverter before setting voltage and frequency
level.
When under the frequency setting press On or when
under battery quantity setting press Off, it goes to the
battery capacity setting. The battery capacity line flashes
as in above picture.
Use button Enter to choose the different battery
capacity. Battery capacity range is 1-200Ah. (Note:
long press of Enter can adjustment battery capa-
city quickly.)
Press or to exit the battery capacity setting
(save the capacity setting) and goes to frequency
setting or battery quantity setting.
Battery
Frequency setting
(Note: Inside the broken line is
the flashing part.)
Battery capacity setting
(Note: Inside the broken line is
the flashing part.)
Input