19
4.3.7 Bypass Volt-Lo setting
4.3.8 Buzzer Mute Setting
When under the bypass voltage upper limit setting press
On▼ or when under Buzzers mute setting press Off▲, it
goes to the bypass lower limit setting. The bypass lower
limit line flashes as in above picture. (“-” for negative,
positive does not have any symbol.)
• Use button Enter (to set the different bypass voltage
lower limit. The bypass voltage lower limit range is
20%,30%,45%.
• Press▲ or ▼ to exit the bypass voltage lower limit
setting (save the bypass voltage lower limit setting)
and goes to bypass upper limit setting or Buzzers
mute setting.
Press ON under bypass voltage lower limit setting or
press OFF under the Battery self-test setting can enter
the buzzer setting. Now the setting status is flashing
as the Figure 14 shows (note: on=mute; off= no mute).
When press, it shows the mute cycle setting, the selec-
tion includes ON and OFF. ( Press the up button or down
button can exit the mute setting (save the mute setting
status) and switch to bypass voltage lower limit setting
or Battery self-test setting (note: when in stand-alone
mode, press down button to exit and save the settings,
then the settings is completed for stand-alone unit).
Bypass voltage lower limit set-
ting (Note: Inside the broken line
is the flashing part.)
Buzzers mute setting (Note:
flashing part in dashed box)