20
4.3.9 Battery Test Setting
This page is the introduction
to the Battery self-test setting.
The default Settings is “OFF”
when the UPS has no need of
the battery self-test function.
When turn to “ON”, batteries
can do the self-test automati-
cally per 30 days. Three kinds
of Battery Self-test Time can be
chosen as below.
When choosing On2, UPS
can transfer to Battery Mode
automatically per 30 days. And
the Battery Self-test Time is 10
minutes.
When choosing On1, UPS
can transfer to Battery Mode
automatically per 30 days. And
the Battery Self-test Time is 10
seconds.
When choosing On3, UPS can
transfer to Battery Mode auto-
matically per 30 days. And the
Battery Self-test Time is EOD.
Battery self-test setting