Installation and start-up of KEOR HPE UPS 60÷160 kVA
Installation et démarrage de l’ASI KEOR HPE 60÷160 kVA
Installazione e avviamento KEOR HPE UPS 60÷160 kVA
4.7 RELAY CARD CONNECTION (OPTIONAL)
The KEOR HPE UPS 60÷160 kVA, in its full configuration, is provided with a relay card for repeating
alarms and operating statuses remotely. The electric connection is carried out directly on the
terminals located on the front of the interfaces slot SRC-2.
Picture 20 – Relay card terminals
Relay Alarms/Status Status
normal
operation
RL1 Alarm = A30 COMMON ALARM
Not energized if
alarm is present
2-3 Closed
DL1 On
1-2 Open
RL2 Alarm = A1 MAINS FAULT
Not energized if
alarm is present
5-6 Closed
DL2 On
4-5 Open
RL3 Alarm = A9 BATTERY AUT END
Not energized if
alarm is present
8-9 Closed
DL3 On
7-8 Open
RL4 Alarm = A13 INV OUT OF TOL
Not energized if
alarm is present
11-12 Closed
DL4 On
10-11 Open
RL5
NORMAL MODE
Alarm = A16 BYPASS LOAD
Not energized if
alarm is present
13-14
14-15
Closed
Open
DL5 On
ECO MODE
Status = S7 BYPASS LOAD
Energized if
status is present
14-15
13-14
Closed
Open
Relay output characteristics:
250 Vac voltage 1 A current
30 Vdc voltage 1 A current resistive load