8 Possible malfunctioning
Error Codes
When the Fault LED
is lit press the ON button
briefly to check the error code.
The error codes 1, 2, 4, 8, and 16 are represented by the four bar LEDs 25%, 50%, 75%, and 100%,
and the Overload LED
.
Each LED represents a number as shown in the figure below.
For example, if the 25%, 50%, and 100% bar LEDs are lit, the error code is therefore 8 + 2 + 1 = 11,
or Er11, which indicates that the UPS is over-temperature.
8
4
2
1
16
Code Meaning
Er05 Battery weak or faulty
Er06 Output short-circuited
Er07 EPO mode
Er11 UPS over-temperature
Er12 Inverter overload
Er24
Utility low (< 160 V)
or battery disconnected
Er28 Bypass overload