44
9 Technical features
MODEL ITEM
3 101 54
3 101 55
3 101 56
3 101 57
3 101 58
3 101 59
Output
Overload
Capacity
(tolerance
+/-1%)
Line
mode
<105% continuous
106-120% for 30 seconds
121-150% for 10 seconds
>150% Immediately transfer to bypass.
Buzzer continuously alarms.
Battery
mode
<105% continuous
106-120% for 30 seconds
121-150% for 10 seconds
>150% Immediately shuts down.
Buzzer continuously alarms.
Bypass
mode
<105% continuous
106-120% for 250 seconds shuts down
121-130% for 125 seconds shuts down
131-135% for 50 seconds shuts down
136-145% for 20 seconds shuts down
Buzzer continuously alarms.
Efficiency
Line mode 90%
Battery mode 85%
ECO mode 96%
Battery
Battery type
12 V/7.2 Ah Sealed, non-spillage,
maintenance-free, lead acid
Number of batteries 2 4 6
Rated Battery Voltage 24 VDC 48 VDC 72 VDC
Backup
time
(Half
Load)
PF=0.7 > 8 min >9 min > 10 min