KEOR T EVO
Installation & Operation Manual
*Rectier protection alone should only be considered in the event of separate inputs; if the bypass and
rectier inputs are combined, the general input protection rating (bypass + rectier) must reect the
recommended bypass or general protection rating.
*Recommended discrimination of UPS downstream distribution with inverter short-circuits current (battery
mode).
**Cables must be selected 1.2 times larger than the recommended size for parallel topologies.
***Must be selective with residual current circuit breakers downstream of the UPS connected to the UPS
output. If the bypass network is separate from the rectier circuit, or in the event of parallel UPS, use a single
residual current circuit breaker upstream of the UPS.
If the loads generates high rate of third harmonic current ( THDI > 33% ), the
current on the common mains supply voltage and auxiliary mains supply voltage
input and output neutral conductors may have a value that is 1.5-2 times the
phase value during operation. In this case, size the neutral cables and the input/
output protection adequately.