18
Display Description Press
Network Settings
Network Status
Panel Network
The Panel Network screen opens, with Network
Settings selected. Press Select
lect
LM Panel 0603981210
Name: 603981210
Device ID: 0 981210
AutoSet MSTPMAC: <Yes>
Auto MSTP MAC: 051
Baud Rate: <38400>
Max Master: <127>
DONE SEND
The top line of the screen shows the serial number
of the panel. The Name defaults to the serial
number, but can be changed. Highlight the value
and press Select to open a new screen, as shown
below.
The Device ID must be a unique number within
the BACnet network. By default, it is set to the last
six digits of the serial number, but like Name can
be changed by highlighting the value and pressing
Select.
The MS/TP MAC address is another ID used to
identify a device. If you select a value of “Yes” for
AutoSet MSTP MAC, the LMCP will select a value
itself, displayed as the Auto MSTP MAC. If you
change the auto set value to “No” and scroll down,
the parameter changes to Manual MSTP MAC and
you can change the value.
The default Baud Rate is 38400, but can be
changed. The Max Master is the highest number
the LMCP will try when polling for a master.
Highlight SEND and press Select.
Once again, point the LMCT-100 at the infrared
sensor on the LMRD board and press Select. You
return to the Panel Network screen.
Highlight DONE and press Select, or press to
return to the Panel Setup screen.
For a detailed explanation of these parameters,
see “Connecting Multiple LMCP Panels in a
Network” on page 30.
then choose
SEND and
or
parameter
or
to change the value
of the parameter
Move to any chacter
with left/right keys.
Change the character
with the up/down keys.
[603981210 ]
DONE ERASE COPY PASTE
If you press Select with the Name or Device
ID field highlighted, this screen opens. You can
change the name using numerals or letters, and
change the ID with numerals only.
Select ERASE to clear all characters before
entering new data.
When finished editing, select DONE to return to the
Network Settings screen.
then choose
DONE and
or
character
or
to change the value
of the character
Viewing the Network Status
The Network Status shows the communication “health” of the network and the number of devices currently found on the network.
Display Description Press
Location Settings
Date and Time
Network
Button Binding
Panel Programming
Status
Panel Setup
From Panel Setup, scroll to Network. Press
Select.
Point to the desired
Panel IR Sensor and
press ‘Select’
Point the LMCT-100 at the infrared sensor on the
LMRD board and press Select.
lect