33
Object Instance Object Alias Object Function
BI101–BI9608 Button state Read button state for 1 to 8 buttons per switch for 1 to 96 switches.
BI1–BI96 Detection state Occupancy sensor detection state. Active = occupied.
BV101–196 Switch lock status Read switch status (locked or unlocked).
Active = locked.
BV201-299 Group Normal Hours/After Hours Normal Hours/After Hours selection for a group.
Active = after hours.
MV4001–MV4096 Daylight sensor 1–96, operating mode For LMLS-400 daylight sensor 1–96, operation mode:
1 = ON/OFF, 2 = bi-level, 3 = tri-level, 4 = dimming.
MV4101–MV4196 Daylight sensor 1–96, setpoint multiplier For LMLS-400, off setpoint multiplier: 1=1.25x, 2=1.50x, 3=1.75x, 4=2x.
Room Level Control Objects
BV1 Schedule state Normal hours/after hours selection. Active = after hours.
NOTE: This changes the status for the entire panel, and therefore can
conflict with BV201-299, if not used carefully.
BV2 Switch lock control Lock or unlock enabled switches. Active = lock.
NOTE: This changes the switch lock status for every switch connected
to the panel, and therefore can conflict with BV101-196, if not
used carefully.
BV3 Room occupancy status Read occupancy status (occupied or unoccupied).
Active = occupied.
NOTE: This is the logical OR of the states of ALL sensors connected
to the panel regardless of their local control scheme. In other
words, if any sensor has a status of occupied, this value will
read occupied.
BV4 Force all loads ON Active = all loads ON at priority 1. Inactive = relinquish at 1 and ON at
priority 8.
NOTE: This will force all loads connected to the panel ON.
BV5 Force all loads OFF Active = all loads OFF at priority 2. Inactive = relinquish.
NOTE: This will force all loads connected to the panel OFF.
MV1 Scene control Write scene selection. Range = 1 to 16.
MV2 Demand response (shed) control Activate room level DR mode: 1 = no shed, 2 = shed mode, permit
switch override, 3 = shed mode, prohibit switch override.
NOTE: This will affect all loads connected to the panel.
AV901 MS/TP MAC address Default is 255 for automatic, writable in the range of 0 to 127.
AV902 MS/TP network speed Baud rate: 9600, 19200, 38400, 57600, 78600, 115200.
AV903 Input room size Allows user to write area in square feet from 0 to 65,534, default is 0.
AV904 Room lighting watts Read total lighting wattage for room.
Total of baseline watts for active relays, or if no baseline wattage for
the relays are used, then this is calculated as AV401 * AV501 + any
usage from LMRC/LMFC connected via CAT5 to the panel.
NOTE: This does not include used from LMPLs. Use AV906 for plug
load controllers.
AV905 Room watts/sq.ft. Read total room lighting W/ft2.
If the input room size for the entire application area is used and the
baseline watts method or AV401 * AV501 method is used, then this
object will calculate the aggregate watts per square foot of the whole
panel’s application area.
Use of this object is not recommended for use in applications where
panels cover mixed areas.
AV906 Room plug load watts Read total plug load wattage for LMPLs connected to the panel.