b-Ifelectrode/flamesensorsparksbuthas"0"voltageat
thevalveduringtriesforignition,checkthewiringbe-
tweenvalveandblower/ignitioncontrol,checkvalve
ground.
c-if electrode/flamesensorsparks24 voltsto valve,
flameis establishedbut does not hold in, check
groundbetweenmoduleandburner,makesurethat
theelectrode/flamesensorisproperlylocatedinthe
middleof theflamestream,checksystemground.
Checktoseeifelectrode/flamesensorislocatedinthe
flamestreamproperly.
d) Ifelectrode/flamesensorsparks24voltstovalvebut
systemfailstoignite,checktomakesurethatthegas
supplyandgasvalveareon,checkto seeif orifice
plugged,andmakesureelectrode/flamesensorare
properlylocated.
Furnace lights and flame rollout occurs or burners have
delayed ignition.
a) Make sure that the carryovers on adjoining burners
are screwed fast and are level with respect to one
another.
b) Make sure electrode/flame sensor is properly located.
c) Make sure all air is purged from gas lines.
Main burners light, but exhibit erratic flame characteristics.
Check the main burner orifices for obstruction and align-
ment. Removal procedure is described in "Burner Instruc-
tions." Clean or replace burner orifices and burners as
needed.
The following blower/ignition control board (DS1) LED
codes will indicate normal or abnormal operations:
Slow Flash
Normal operation, no call for heat
One flash per second
Fast Flash
Normal operation, call for heat
Two flashes per second.
2 Flash
System lockout - failed to detect or sustain flame
Two flashes in one second with a one second pause.
3 Flash
Pressure switch open or closed
Three flashes in one and one-half seconds with a one sec-
ond pause.
4 Flash
High limit/or rollout switch open
Four flash in two seconds with a one second pause.
5 Flash
Flame sensed and gas valve not energized
Five flashes in two and one-half seconds with a one second
pause.
Steady
Internal failure (micro-controller failure; self-check)
The following repair parts are available from your local dealer. When ordering parts, include the complete model number
and serial number which are printed on the unit rating plate.
Control Group
Rollout Switch
Transformer
Limit Control
Gas Valve
Blower/Ignition Control
Electrode
Flame Sensor
Auxiliary Limit
Pressure Switch
Blower Group
Blower Housing Assembly
Blower Wheel
Blower Motor
Blower Motor Mount
Blower Motor Capacitor (if used)
Combustion Air Inducer
Fan Blade
Fan Motor
Fan Motor Capacitor
Heating Group
Gas Manifold
Main Burner Orifices
Main Burners
Heat Exchanger
Cooling Group
Compressor
Evaporator Coil
Drier
Cap. Tube or Expansion Valve
Contactor
Capacitor
Condenser Coil
Accessories
LENNOX Cat.
Description Kit Number
Number
Low Ambient Control ALOAM 111-1 42K88
High Pressure Cut-out Kit AHPSW436-1 42K89
Timed Off Control ATIMR446-1 42K90
LP Gas Conversion ALPKTS533-1 42K91
Page 16

Related product manuals