l/h kPa kW kW kW
10 °C
1530 25 --- --- --- 9,77 3,56
2190 40 --- --- --- 10,06 3,60
3130 65 --- --- --- 10,24 3,64
15 °C
1530 25 11,19 6,05 0,68 10,85 3,73
2190 40 11,30 6,29 0,67 11,17 3,77
3130 65 11,37 6,53 0,67 11,39 3,80
20 °C
1530 25 10,85 5,20 0,68 11,96 3,86
2190 40 10,97 5,42 0,68 12,30 3,90
3130 65 11,04 5,62 0,68 12,55 3,92
25 °C
1530 25 10,48 4,46 0,69 13,10 3,96
2190 40 10,60 4,66 0,69 13,46 3,99
3130 65 10,68 4,83 0,69 13,75 4,01
30 °C
1530 25 10,07 3,83 0,70 --- ---
2190 40 10,20 4,00 0,70 --- ---
3130 65 10,29 4,14 0,70 --- ---
35 °C
1530 25 9,63 3,30 0,72 --- ---
2190 40 9,76 3,45 0,71 --- ---
3130 65 9,86 3,56 0,71 --- ---
40 °C
1530 25 9,15 2,89 0,73 --- ---
2190 40 9,29 3,01 0,73 --- ---
3130 65 9,39 3,09 0,72 --- ---
l/h kPa kW kW kW
10 °C
1690 30 --- --- --- 10,74 3,52
2410 48 --- --- --- 11,05 3,56
3440 75 --- --- --- 11,25 3,59
15 °C
1690 30 12,37 6,05 0,66 11,94 3,67
2410 48 12,50 6,29 0,66 12,26 3,70
3440 75 12,59 6,50 0,66 12,50 3,72
20 °C
1690 30 11,96 5,20 0,67 13,15 3,77
2410 48 12,10 5,42 0,67 13,50 3,80
3440 75 12,18 5,61 0,67 13,77 3,81
25 °C
1690 30 11,52 4,46 0,68 14,38 3,84
2410 48 11,66 4,66 0,68 14,75 3,86
3440 75 11,75 4,82 0,67 15,05 3,87
30 °C
1690 30 11,06 3,83 0,69 --- ---
2410 48 11,20 4,00 0,68 --- ---
3440 75 11,30 4,13 0,68 --- ---
35 °C
1690 30 10,57 3,29 0,70 --- ---
2410 48 10,71 3,45 0,70 --- ---
3440 75 10,82 3,55 0,69 --- ---
40 °C
1690 30 10,06 2,87 0,71 --- ---
2410 48 10,20 3,00 0,71 --- ---
3440 75 10,31 3,07 0,71 --- ---
AWH 010
1.900 m
3
/h
AWH 012
2.000 m
3
/h
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
GENERAL CHARACTERISTICS
1.8.- CAPACITY TABLES
Water ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Water ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal operating conditions:
Exchanger air inlet temperature: 27ºC DB/19ºC WB in cooling mode and 20ºC WB
in heating mode.
(DW:dry bulb / WB:wet bulb)
For another working conditions use correction factor tables.