• 14 •
AWC
--
007 008 010 012 015 018 020
AWH
002 003
l/h
- - 20 25 30 35 35 40 45
- - 30 35 50 55 55 60 75
- - 45 60 80 90 80 100 115
l/h kPa kW kW kW
10 °C
2860 35 --- --- --- 17,65 3,43
4090 55 --- --- --- 18,13 3,46
5840 80 --- --- --- 18,45 3,48
15 °C
2860 35 20,89 5,68 0,65 19,53 3,54
4090 55 21,12 5,88 0,65 20,06 3,57
5840 80 21,25 6,04 0,65 20,42 3,58
20 °C
2860 35 20,23 5,01 0,66 21,44 3,63
4090 55 20,46 5,20 0,66 22,00 3,65
5840 80 20,60 5,34 0,66 22,42 3,66
25 °C
2860 35 19,52 4,40 0,67 23,37 3,69
4090 55 19,75 4,57 0,67 23,97 3,71
5840 80 19,90 4,70 0,66 24,44 3,72
30 °C
2860 35 18,76 3,83 0,68 --- ---
4090 55 19,00 4,00 0,67 --- ---
5840 80 19,16 4,11 0,67 --- ---
35 °C
2860 35 17,96 3,33 0,69 --- ---
4090 55 18,20 3,48 0,68 --- ---
5840 80 18,36 3,58 0,68 --- ---
40 °C
2860 35 17,11 2,88 0,70 --- ---
4090 55 17,36 3,02 0,69 --- ---
5840 80 17,53 3,10 0,69 --- ---
AWH 020
3.100 m
3
/h
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
1.8.- CAPACITY TABLES
Minimum water ow
Nominal water ow
Maximum water ow
Dissipated heat for cooling mode:
The heat to dissipate in the water exchanger for cooling mode is near to: Total capacity + Total absorbed power.
Absorbed heat for heating mode:
The heat absorbed in the water exchanger for heating mode is near to: Total capacity - Total absorbed power.
WATER PRESSURE DROP WITH WATER FILTER AWC/AWH
Water pressure drop has been calculated without water lter option. With this option, the water pressure drop (kPa) would
be :
GENERAL CHARACTERISTICS
Water ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal operating conditions:
Exchanger air inlet temperature: 27ºC DB/19ºC WB in cooling mode and 20ºC WB
in heating mode.
(DW:dry bulb / WB:wet bulb)
For another working conditions use correction factor tables.
Nominal air ow rate