Page 13
TABLE 3 
Integrated Control Diagnostic Modes
Display Action (when button released)
No Change Remain in idle mode
Solid “E” Enter diagnostic recall mode
Solid “F” Enter ame signal mode
TABLE 4 
Integrated Diagnostic Codes/Status of Equipment
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
. Idle mode (Decimal blinks at 1 Hertz -- 0.5 
second ON, 0.5 second OFF).
C Cooling stage (1 second ON, 0.5 second OFF) 
1 or 2 displayed / Pause / Repeat codes.
d Dehumidication mode (1 second ON, 1 
second OFF) / Pause / Repeat Codes).
H Gas Heat Stage (1 second ON, 0.5 second 
OFF) 1 or 2 displayed / Pause / Repeat codes. 
Blinking during ignition.
h Heat pump stage.
E110 Low line voltage. Line Voltage Low (Voltage lower than nameplate rating). Check power 
line voltage and correct. Alarm clears 5 seconds after fault recovered.
E111 Line voltage polarity reversed. Reverse line power voltage wiring. System resumes normal operation 
5 seconds after fault recovered.
E112 Ground not detected. System shuts down. Provide proper earth ground. System resumes 
normal operation 5 seconds after fault recovered.
E113 High line voltage. Line Voltage High (Voltage higher than nameplate rating). Provide 
power voltage within proper range. System resumes normal operation 
5 seconds after fault recovered.
E114 Line voltage frequency out-of-range. No 60 Hertz Power. Check voltage and line power frequency. Correct 
voltage and frequency problems. System resumes normal operation 5 
seconds after fault recovered.
E115 Low 24V - Control will restart if the error 
recovers.
24-Volt Power Low (Range is 18 to 30 volts). Check and correct 
voltage. Check for additional power-robbing equipment connected 
to system. May require installation of larger VA transformer to be 
installed in furnace / air handler. Clears after fault recovered.
E117 Poor ground detected (Warning only). Provide proper grounding for unit. Check for proper earth ground to 
the system. Warning only will clear 30 seconds after fault recovered.
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal, active error code, heat state, etc.)
Diagnostic LED
The  seven-segment  diagnostic  LED  displays  operating 
status, error codes and other information. Table be4 lists 
diagnostic LED codes.
Diagnostic Push Button
The diagnostic push button is located adjacent to the sev-
en-segment diagnostic LED. This button is used to enable 
the  Error  Code  Recall  “E”  mode  and  the  Flame  Signal 
“F” mode. Press the button and hold it to cycle through a 
menu of options. Every ve seconds a new menu item will 
be displayed. When the button is released, the displayed 
item  will  be  selected.  Once  all  items  in  the  menu  have 
been  displayed,  the  menu  resumes  from  the  beginning 
until the button is released.
Error Code Recall Mode
Select  ”E”  from  the  menu  to  access  the  most  recent  10 
error codes. Select “c” from the Error Code Recall menu 
to clear all error codes. Button must be pressed a second 
time  while  “c”  is  ashing  to  conrm  command  to  delete 
codes.
Press the button  until  a solid “≡”  is  displayed to exit  the 
Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the ame signal mode. 
The  integrated  control  will  display  the  ame  current  on 
seven-segment LED in in micro amps (uA). Flame signal 
mode is exited after any of the following:
•    Power is reset
•    Pressing and holding push button until 3 horizontal lines “≡” are 
displayed
•    10 minutes after entering the ame sense mode.