Page 32
Cleaning the Heat Exchanger and Burners
NOTE - Use papers or protective covering in front of the 
furnace during cleaning.
1 -   Turn  o  both  electrical  and  gas  power  supplies  to 
furnace.
2 -   Remove ue pipe and top cap (some applications 
top cap can remain) from the unit.
3 -   Label  the  wires  from  gas  valve,  rollout  switches, 
primary  limit  switch  and  make-up  box  then 
disconnect them.
4 -   Remove the screws that secure the combustion air 
inducer/ pressure switch assembly to the collector 
box.  Carefully  remove  the  combustion  air  inducer 
to  avoid  damaging  blower  gasket.  If  gasket  is 
damaged, it must be replaced to prevent leakage.
5 -   Remove  the  collector  box  located  behind  the 
combustion air inducer. Be careful with the collector 
box  gasket.  If  the  gasket  is  damaged,  it  must  be 
replaced to prevent leakage.
6 -   Disconnect  gas  supply  piping.  Remove  the screw 
securing  the  burner  box  cover  and  remove  cover. 
Remove  the  four  screws  securing  the  burner 
manifold  assembly  to  the  vestibule  panel  and 
remove the assembly from the unit.
7 -   Remove  screws  securing  burner  box  and remove 
burner box.
8 -   NOX units only -  Remove  screw  securing  NOX 
insert. Remove NOX insert. FIGURE 25.
9 -  Remove screws from both sides, top and bottom of 
vestibule panel.
10 -  Remove  heat  exchanger.  It  may  be  necessary 
to  spread  cabinet  side  to  allow  more  room.  If  so, 
remove ve screws from the left side or right side of 
cabinet. See FIGURE 26.
11 -  Backwash  using  steam.  Begin  from  the  burner 
opening  on  each  clam.  Steam  must  not  exceed 
275°F.
12 -   To clean burners, run a vacuum cleaner with a soft 
brush attachment over the face of burners. Visually 
inspect inside  the burners  and crossovers  for any 
blockage  caused  by  foreign  matter.  Remove  any 
blockage. FIGURE 24 shows burner detail.
13 -  To clean the combustion air inducer visually inspect 
and using a wire brush clean where necessary. Use 
compressed air to clean o debris and any rust.
14 -  Reinstall heat exchanger in vestibule. (Replace the 
ve screws in the cabinet from step 10 if removed).
15 -  NOx units only - Replace NOx inserts.
16 -  Reinstall  collector  box  and  combustion  air 
assembly. Reinstall all  screws  to  the  collector  box 
and  combustion  air  inducer.  Failure  to  replace  all 
screws  may  cause  leaks.  Inspect  gaskets  for  any 
damage and replace ifw necessary.
17 -  Reinstall burner box, manifold assembly and burner 
box cover.
18 -  Reconnect all wires.
19 -  Reconnect top cap and vent pipe to combustion air 
inducer outlet.
20 -  Reconnect gas supply piping.
21 -  Turn on power and gas supply to unit.
22 -  Set thermostat and check for proper operation.
23 -  Check all piping connections, factory and eld, for 
gas  leaks.  Use  a  leak  detecting  solution  or  other 
preferred means.
 WARNING
Some soaps used for leak detection are corrosive 
to certain metals. Carefully rinse piping thoroughly 
after leak test has been completed. Do not use 
matches, candles, ame or other sources of ignition 
to check for gas leaks.
24 -  If a leak is detected, shut gas and electricity o and 
repair leak.
25 -  Repeat steps 24 and 26 until no leaks are detected.
26 - 26 -Replace access panel.