When  the  dierential  in  the  pressure  switch  is  great 
enough, the pressure switch closes and a 15-second pre-
purge begins .
After the 15-second pre-purge  period, the SureLight
®
 ig-
nitor warms up for 20 seconds after which the gas valve 
opens for a 4-second trial for ignition. The ignitor remains 
energized during the trial until ame is sensed. If ignition 
is not proved during the 4-second period, the control will 
try four more times with an inter purge and warm-up time 
between  trials  of  35  seconds. After  a  total  of  ve  trials 
for ignition(including the initial trial), the control goes into 
Watchguard- Flame Failure mode. After a 60-minute reset 
period, the control will begin the ignition sequence again.
NOTE - During abnormal conditions such as low supply 
voltage or low outdoor temperatures and the low re pres-
sure switch does not close, the combustion air inducer will 
switch to high speed. After the low & high pressure switch 
close, the unit will proceed with a 15 sec pre-purge, fol-
lowed by a 20 sec ignitor warm up, then ignition on high-
re. After 10 to 20 seconds of high re operation the unit 
will switch to low re.
Two Stage Operation / Thermostat Selection DIP 
Switch
The control can be utilized in two modes: SINGLE-STAGE 
thermostat  or  TWO-STAGE  thermostat.  The  thermo-
stat  selection  is  made  using  a  DIP  switch  and  must  be 
positioned  for  the  particular  application.  DIP  switch  1, 
labeled  T”STAT  HEAT  STAGE  is  factory-set  in  the  OFF 
position  for  use  with  a  two-stage  thermostat.  Move  the 
DIP switch to ON for use with a single stage thermostat. 
While  in  the  single-stage  thermostat  mode,  the  burners 
will always re on rst-stage heat. The combustion air in-
ducer  will  operate  on  low  speed  and  indoor  blower  will 
operate on low heat speed.
 
The unit will switch to second stage heat  after a “recog-
nition  period”.  DIP  switch  2,  labeled  SECOND  STAGE 
DELAY, is factory  set in the OFF position  for a 7 minute 
recognition period. The  switch  can be  moved  to the  ON 
position  for  a  12  minute  recognition  period,  after  which 
time the unit will switch to second-stage heat. While in the 
two-stage thermostat mode, the burners will re on rst-
stage heat. The combustion air inducer will operate on low 
speed and indoor blower will operate on low heat speed.
 The unit will switch to second-stage heat on call from the 
indoor thermostat. If there is a simultaneous call for rst 
and second stage heat, the unit will re on rst stage heat 
and switch to second stage heat after 30 seconds of oper-
ation. See Sequence of Operation ow charts in the back 
of this manual for more detail.
TABLE 1 
SureLight
®
 Control 5 Pin Terminal Designation
Pin # Function
1 Ignitor
2 Combustion Air Inducer High Speed
3 Combustion Air Inducer Low Speed
4 Combustion Air Inducer Neutral
5 Ignitor Neutral
TABLE 2 
SureLight
® 
Control 12 Pin Terminal Designation
Pin # Function
1 Gas Valve Second Stage
2 Pressure Switch Second Stage
3 Rolout Switch
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve First Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Out
12 Pressure Switch First Stage