Page 18
DIFFERENTIAL SWITCH CLOSED
-1.0-0.20
-1.0
-0.2
0
-0.4
-0.6
-0.8
-1.2
-0.4 -0.6 -0.8 -1.2
BURNER BOX STATIC PRESSURE
COMBUSTION AIR BLOWER STATIC PRESSURE
DIFFERENTIAL SWITCH OPEN
(Furnace will not operate)
CHART REPESENTS NORMAL OPERATING
CHARACTERISTICS OF THE PRESSURE SWITCH ONLY
AND SHOULD NOT BE USED FOR TROUBLSHOOTING
FIGURE 24
Temporarily jumpering the pressure switch when troubleĆ
shooting will determine if the pressure switch and furnace
are operating properly. However, this may not indicate if
the sealed combustion system is operating properly. If the
unit cannot attain 0.2 inches differential, the unit will not
operate. Be sure to remove jumper when finished. See
Warning this page.
WARNING
Safety Hazard. Turn off gas supply before jumpĆ
ering  switch  or  testing  switch  differential.  If
switch is operating  properly  and  sealed comĆ
bustion system is operating improperly, a poĆ
tentially  lethal  situation  will  be  created  when
switch is bypassed. DO NOT ALLOW UNIT TO
OPERATE WITH SAFETY SYSTEMS BYPASSED.
Checks of pressure differential can be made as an aid in trouĆ
bleshooting. It is important to remember that the switch must
see" 0.2 inches differential in order for the furnace to operate.
Lack of differential usually indicates problems in the intake or
exhaust  piping  but  may  indicate  problems  in  the  heat  exĆ
changer, condenser coil, header boxes, combustion blower or
other  components.  Generally, if  both readings  are  closer  to
zero (figure 24) the unit may have a restricted flue outlet or
other problem. If both readings are farther from zero (figure
24) the unit may have a restricted flue inlet or other problem.
Measuring pressure differential
The differential pressure is the difference in pressure meaĆ
sured on either side of the pressure switch:
1 - Remove thermostat demand and allow to cycle off.
2 - Disconnect hose from left side of pressure switch and
install Tee as shown in figure 25.
FIGURE 25
TEE AND 1/4"i.d. RUBBER HOSE FIELD
PROVIDED
USED FOR MEASURING PRESĆ
SURE  ACROSS BURNER BOX
AND COMBUSTION AIR BLOWER
TO DRAFT GAUGE
TO PRESSURE
SWITCH
TO PRESSURE
SENSING HOSE
3 - Install draft gauge to open end of Tee.
4 - Operate unit and observe draft gauge reading. ReadĆ
ings will change as heat exchanger warms.
a. Take one reading immediately after startup.
b.  Take  a  second  reading  after  unit  has  reached
steady state (approximately 5 minutes).
5 - Remove thermostat demand and allow to cycle off.
6 - Remove draft gauge and Tee. Reinstall combustion air
sensing hose to left side of pressure switch.
7 - Disconnect hose  from right  side of  pressure switch
and install Tee as shown in figure 25.
8 - Install draft gauge to open end of Tee.