Page 26
TABLE 13
G32V3-75 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Blower Speed Adjustment Settings (Switches 5 and 6)
Cool
Adjust"
Low Speed High Speed
Setting
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 880 415 930 440 980 465 1040 490 1060 500 1105 520 1260 595 1330 630
ć
775 365 810 380 850 400 910 430 930 440 970 460 1070 505 1130 535
Blower Speed Adjustment Settings (Switches 7 and 8)
Heat
Adjust"
Low Speed High Speed
Setting
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 945 446 1025 484 1125 531 1270 599 1080 510 1172 533 1286 607 1452 685
ć
803 379 871 411 956 451 1080 510 918 433 996 470 1093 516 1234 582
15% lower motor speed than NORM switch setting.
NOTE - The effect of static pressure and filter resistance is included in air volumes shown.
NOTE - Continuous Fan only speed is approximately 800 cfm (380 L/s) - non adjustable.
NOTE - Lennox Harmony IIt zone control applications - MAX CFM is determined by COOL switch setting with a minimum of approximately 850
cfm (400 L/s) for all positions.
TABLE 14
G32V5-100/125 BLOWER MOTOR PERFORMANCE
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Blower Speed Adjustment Settings (Switches 5 and 6)
Cool
Adjust"
Low Speed High Speed
Setting
1
2
3 4 1
2
3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 1140 540 1250 590 1440 680 1550 730 1620 765 1820 860 2000 945 2100 990
ć
970 455 1060 500 1280 605 1320 595 1380 650 1550 730 1700 800 1780 840
Blower Speed Adjustment Settings (Switches 7 and 8)
Heat
Adjust"
Low Speed High Speed
Setting
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
Norm 1140 540 1250 590 1440 680 1550 730 1560 735 1720 810 2030 960 2150 1015
ć
970 455 1060 500 1280 605 1320 595 1330 660 1460 690 1730 815 1830 865
15% lower motor speed than NORM switch setting.
G32V5-125 Models Only - Do not set switches for position #1 (at NORM or ć" setting) or position #2 (at -" setting) for HEAT speed.
NOTE - The effect of static pressure and filter resistance is included in air volumes shown.
NOTE - Continuous Fan only speed is approximately 1150 cfm (545 L/s) - non adjustable.
NOTE - Lennox Harmony IIt zone control applications - MAX CFM is determined by COOL switch setting with a minimum of approximately 1140
cfm (540 L/s) for all positions.