LED#1−Slow Flash
LED#2−Fast Flash
6.1.2
Sensor rod is contaminated.
ACTION 1 − Check sensor rod for contamination
or coated surface. Clean the sensor rod with steel
wool or replace sensor. DO NOT USE SAND PA-
PER TO CLEAN ROD. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM.
PROBLEM 7: INDOOR BLOWER FAILS TO OPERATE IN COOLING, HEATING, OR CONTINUOUS
FAN MODE
Condition Possible Cause Corrective Action/Comments
7.0
− Indoor blower fails to operate in
continuous fan, cooling, or heating
mode.
7.1.1
Miswiring of furnace or improper
connections at control or indoor blow-
er motor.
ACTION 1− Correct wiring and/or replace any
loose connections. Check for correct wiring and
loose connections.
7.1.2
120V is not being supplied to the
indoor air blower or blower motor fail-
ure.
ACTION 1 − Check for 120V at the various calls for
indoor blower by energizing "Y", "G", and "W" indi-
vidually on the low voltage terminal strip. Note that
when "W’ is energized, the blower is delayed 45
seconds. If there is 120V to each motor tap but the
blower does not operate, replace the motor.
7.1.3
Defective control board
ACTION 1 − If there is not 120V when "Y", "G", or
"W" is energized, replace the control.
7.1.4
Defective run capacitor
ACTION 1 − Replace capacitor
PROBLEM 8: RF STATIC DURING TIME FOR IGNITION
Condition Possible Cause Corrective Action/Comments
8.0
− AM radio interference.
8.1.2
Ignitor operation
ACTION 1 − Call Technical Support, Dallas.