Page 3
SPECIFICATIONS
Gas
Heating
Performance
ModelNo. G60UHV−60C−110 G60UHV−60D−135
Low NOx Model No. G60UHV−60C−110X − − −
Input− Btuh (kW) low fire 75,000 (22.0) 90,000 (26.4)
Output− Btuh (kW) low fire 60,000 (17.6) 72,000 (21.1)
Input− Btuh (kW) high fire 110,000 (32.2) 132,000 (38.7)
Output− Btuh (kW) high fire 90,000 (26.4) 108,000 (31.6)
AFUE 80.0% 80.0%
California Seasonal Efficiency 77.2% 77.5%
Highstatic(CSA)− in.w.g. (Pa) .80 (200) .80 (200)
Flue connection − in. (mm) round 4 (102) 4 (102)
GaspipesizeIPS− in. (mm) 1/2 (12.7) 1/2 (12.7)
Temperature rise range − F (C) low fire 25 − 55 (14 − 31) 25 − 55 (14 − 31)
Temperature rise range − F (C) high fire 35 − 65 (19 − 36) 45 − 75 (25 − 42)
Indoor
Blower
Wheelnominaldiameter xwidth −in. (mm) 11−1/2 x 10 (292 x 254) 11−1/2 x 10 (292 x 254)
Motoroutput − hp (W) 1 (746) 1 (746)
Tons(kW) ofadd-oncooling 4 − 5 (14.1 − 17.6) 4 − 5 (14.1 − 17.6)
Shippingweight − 1 package 184 (83) 198 (90)
Matching Coils
Up−flow cased
C33−36C−2F, C33−48C−2F,
C33−50/60C−2F,
C33−60D−2F, C33−62D−2F
Horizontal
CH33−36C−2F, CH33−48C−2F,
CH33−50/60C−2F
CH33−60D−2F, CH33−62D−2F
Electricalcharacteristics 120 volts − 60 hertz − 1 phase (less than 12 amps)
OPTIONAL ACCESSORIES − MUST BE ORDERED EXTRA
Air Filter and Rack Kit
Number and size of filters
Horizontal (end)
87L97
(1) 20 x 25 x 1 in. (508 x 635 x 25
mm)
87L98
(1) 25 x 25 x 1 in. (635 x 635 x 25
mm)
Side Return Single 44J22 or Ten Pack (66K63) − (1) 16 x 25 x 1 (406 x 635 x 25)
EZ Filter Base
Catalog Number − Shipping Weight 73P57 − 8 lbs. (4 kg) 73P58 − 10 lbs. (5 kg)
Dimensions − H x W x D
4 x 21−5/8 x 28−5/8 in.
(102 x 549 x 727 mm)
4 x 24−5/8 x 28−5/8 in.
(102 x 625 x 727 mm)
Number and size of field provided filter (1) 20 x 25 x 1 in. (508 x 635 x25 mm)
(1) 24 x 24 x 1 in. (610 x 610 x 25
mm)
CCB1 Efficiency Plust Humidity Control System 35H00 35H00
High Altitude Pressure Switch Kit See Page 7
Horizontal Support Frame Kit − Shipping Weight 56J18 − 18 lbs. (8 kg) 56J18 − 18 lbs. (8 kg)
LPG/Propane Kit See Page 7
RAB Return Air Base RAB60C (12M71) RAB60D (12M72)
Vent Adaptor − 6 in. 152 (mm) connection size 18M79 − 2 lbs. (1 kg) 18M79 − 2 lbs. (1 kg)
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
NOTE − Filters and provisions for mounting are not furnished and must be field provided.
The same C33 uncased models match the furnaces shown but require an optional adaptor base or field fabricated transition. See C33 coil bulletin for additional information.
Cleanable polyurethane frame type filter.
Flue connection on the unit is 4 in. (102 mm) diameter. Most applications will require 5 in. (127 mm) venting and field supplied 4 x 5 in. (102 x 127 mm) adaptor. See Venting
Tables in the Installation Instructions for detailed information.
Not for use with RAB Return Air Base or with 60C and 60D size units with 2nd stage heating air flow requirements of 1800 cfm (850 L/s) or greater. See Blower Performance
Tables for additional information.