EasyManuals Logo
Home>Lennox>Air Conditioner>MPB018S4M

Lennox MPB018S4M User Manual

Lennox MPB018S4M
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #123 background imageLoading...
Page #123 background image
123
Error Code: P4
Description: Hightemperaturesensedatcompressordischargeline.
General Note: Whenthecompressordischargetemperature(T5)ismorethan239°F(115°C)for10seconds,thecompressorwillstopand
restarttillT5islessthan194°F(90°C).
Temperatureprotectionofcompressor.
Checkwhetherthecompressordischargetemp.is
morethan239°F(115°C)?
No
Checkwhethertheconnectionisrightbetweencom-
pressordischargetemp.sensorandPCBaccordingto
wiringdiagrams?
Checkwhetherthe
refrigerantisleak.
Yes
Stopleakingandadd
refrigerant.
Yes
No
Correctthewiringconnection.
No
Yes
Measuretheresistancevalueofcompressordis-
chargetemp.sensor.Ifthevalueisnotnormalis
normalrefertotheAppendix2?
Replacethecompressor
dischargetemp.sensor.
No
Yes
ReplaceoutdoormainPCB.
No
Replacehighpressurevalveassy.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MPB018S4M and is the answer not in the manual?

Lennox MPB018S4M Specifications

General IconGeneral
BrandLennox
ModelMPB018S4M
CategoryAir Conditioner
LanguageEnglish

Related product manuals