EasyManua.ls Logo

Lennox OF23Q3/4-105 - Page 7

Lennox OF23Q3/4-105
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 7
Front Flue / Masonry Chimney
Rear Flue / Masonry Chimney
clean out
clean out
liner
masonry
chimney
barometric
control*
(in either location)
clean out
clean out
liner
masonry
chimney
Figure 6
*Barometric control may be installed in either vertical or hori-
zontal section of flue pipe within 18" of flue outlet of furnace.
barometric
control*
(in either location)
10− Extend the vent pipe into the chimney so that it is flush
with the inside of the vent liner. Seal the joint between
the pipe and the liner.
11 The furnace shall be connected to a factory built chim-
ney or vent complying with a recognized standard, or
masonry or concrete chimney lined with a lining mate-
rial acceptable to the authority having jurisdiction.
12− When two or more appliances vent into a common
vent, the area of the common vent should not be less
than the area of the largest vent or vent connection
plus 50% of the area of the additional vent or vent con-
nection. Chimney must be able to sufficiently vent all
appliances operating at the same time.
13− The vent pipe shall not be connected to a chimney
vent serving a solid fuel appliance or any mechanical
draft system.
14− All unused chimney openings should be closed.
15 All vent pipe run through unconditioned areas or out-
side shall be constructed of factory built chimney sec-
tions. See figure 7.
16− Where condensation of vent gas is apparent, the vent
should be repaired or replaced. Accumulation of con-
densation in the vent is unacceptable.
17− Vent connectors serving this appliance shall not be
connected into any portion of mechanical draft sys-
tems operating under positive pressure.
18− Keep the area around the vent terminal free of snow,
ice and debris.
NOTE − If vent pipe needs to exit from side of cabinet,
use the pilot hole (located on either side of the unit) to
cut a 6" (152 mm) round hole. Attach finishing plate
(provided) with four sheet metal screws to cover rough
edges.
Front Flue / Factory−Built Chimney
Rear Flue / Factory−Built Chimney
Figure 7
*Barometric control may be installed in either vertical or hori-
zontal section of flue pipe within 18" of flue outlet of furnace.
drain for
condensate
factory
built
chimney
drain for
condensate
factory
built
chimney
barometric
control*
(in either location)
barometric
control*
(in either location)

Related product manuals