Page 7
HORIZONTAL APPLICAT ION
FRONT VIEW
AIR FLOW
END VIEW
UNIT
FRONT
1/2”
max.
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
FRONT VIEW
SIDE VIEW
1/2” max.
AIR FLOW
UNIT
FRONT
SIDE VIEW
UNIT
FRONT
UPFLOW APPLICATION
FIGURE 5
(with transition and filter)
Return
Air
Plenum
20” X 25” X 1”
(508mmX635mmX 25mm
Air Filter
1−1/2”
FIGURE 6
SLP98UHV applications which include side return air
and a condensate trap installed on the same side of
the cabinet (trap can be installed remotely within 5
feet) require either a return air base or eld-fabricated
transition to accommodate an optional IAQ accessory
taller than 14.5”. See gure 6.
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See gure 7.
Removing the Bottom Panel
Screw
Bottom Panel
Bottom Cap
FIGURE 7