SLP98UHV / Page 20
BLOWER DATA
SLP98UH070XV36B BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 489 538 636 735 833 931 1030 1128
Increase (+7.5%) Heat CFM 450 496 588 680 772 864 956 1048
Default Heat CFM 410 453 539 624 710 796 881 967
Decrease (-7.5% ) Heat CFM 380 419 498 578 657 736 815 895
Decrease (-15% ) Heat CFM 349 385 458 531 604 676 749 822
SLP98UH070XV36B BLOWER MOTOR WATTS - COOLING
Blower Speed
Options
Motor Watts @ Various External Static Pressures - in. wg.
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Increase (+10%) Cool CFM
Low 22 36 51 60 80 95 101 117 138 68 88 105 129 152 169 198 214 231 244 274
Medium-Low 37 57 75 89 106 127 148 168 182 121 144 168 192 211 243 262 287 305 329 358
Medium-High 62 85 97 122 144 164 180 203 220 213 231 259 285 311 328 357 374 397 419 445
High 88 115 132 155 176 203 233 240 274 304 322 359 379 411 442 458 486 502 527 554
Default Cool CFM
Low 16 29 42 55 71 82 98 112 120 52 69 86 107 122 146 165 183 199 212 229
Medium-Low 26 41 63 79 88 112 128 145 159 89 108 135 151 174 198 223 247 268 288 298
Medium-High 39 62 77 96 117 140 156 180 196 151 173 201 225 243 266 289 313 339 368 383
High 65 84 104 125 148 166 178 206 225 237 256 284 303 328 343 374 395 421 435 454
Decrease (-10%) Cool CFM
Low 11 21 35 53 64 75 82 95 113 34 50 67 86 106 121 141 159 174 186 201
Medium-Low 21 36 51 66 81 92 107 127 141 64 85 100 114 145 160 182 206 219 237 251
Medium-High 35 48 66 82 104 118 137 146 159 101 125 143 171 193 211 242 258 282 304 330
High 43 60 82 100 123 144 159 174 197 161 188 211 229 258 277 307 327 354 379 404
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 600 740 840 970 860 1060 1215 1365
Default Cool CFM 555 665 770 855 810 960 1130 1265
Decrease (-10%) Cool CFM 500 600 680 790 705 840 1005 1140
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.