SLP98UHV / Page 31
BLOWER DATA
SLP98UH090XV60C BLOWER PERFORMANCE (less lter)
SINGLE SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 611 686 837 987 1138 1288 1439 1589
Increase (+7.5%) Heat CFM 554 626 771 916 1060 1205 1349 1494
Default Heat CFM 497 566 705 844 983 1121 1260 1399
Decrease (-7.5% ) Heat CFM 436 502 633 764 895 1026 1157 1288
Decrease (-15% ) Heat CFM 375 437 560 683 806 930 1053 1176
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 1035 1230 1390 1565 1560 1740 1940 2145
Default Cool CFM 950 1085 1235 1405 1410 1585 1785 1975
Decrease (-10%) Cool CFM 855 995 1085 1235 1260 1430 1595 1785
SLP98UH090XV60C BLOWER MOTOR WATTS - COOLING
Blower Speed
Options
Motor Watts @ Various External Static Pressures - in. wg.
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Increase (+10%) Cool CFM
Low 66 96 123 140 167 199 223 253 282 238 262 319 353 395 431 467 499 531 576 614
Medium-Low 106 136 174 202 240 269 305 335 364 331 375 420 463 523 564 610 661 719 742 780
Medium-High 153 194 224 265 302 340 379 412 453 502 533 602 651 714 772 809 856 899 952 989
High 238 262 319 353 395 431 467 499 531 703 745 799 877 932 969 1020 1070 1122 1142 1169
Default Cool CFM
Low 53 76 101 120 143 162 187 208 238 172 203 240 278 316 354 394 420 459 489 519
Medium-Low 76 110 132 153 189 222 246 274 304 260 290 344 383 415 468 498 533 580 619 653
Medium-High 110 142 178 207 247 285 313 346 375 354 396 445 500 546 604 652 695 747 766 837
High 172 203 240 278 316 354 394 420 459 539 575 623 692 733 798 831 885 926 980 997
Decrease (-10%) Cool CFM
Low 36 53 73 101 121 141 159 177 196 119 159 186 211 248 289 318 353 389 418 446
Medium-Low 54 83 106 129 148 175 204 231 258 185 215 250 294 334 377 407 450 472 503 545
Medium-High 76 110 132 153 189 222 246 274 304 263 302 351 383 419 474 497 548 587 636 663
High 119 159 186 211 248 289 318 353 389 379 422 472 519 571 623 659 716 759 804 841
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.