SLP98UHV / Page 32
BLOWER DATA
SLP98UH110XV60C BLOWER PERFORMANCE (less lter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35% 40% 50% 60% 70% 80% 90% 100%
Increase (+15%) Heat CFM 767 861 1049 1237 1424 1612 1800 1988
Increase (+7.5%) Heat CFM 738 825 1000 1174 1349 1524 1699 1874
Default Heat CFM 708 789 951 1112 1274 1436 1597 1759
Decrease (-7.5% ) Heat CFM 655 731 883 1035 1187 1339 1491 1644
Decrease (-15% ) Heat CFM 602 673 816 958 1101 1243 1386 1528
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm Second Stage Cool Speed - cfm
Low Medium-
Low
Medium
High
High
(Default)
Low Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM 1060 1245 1345 1545 1560 1740 1930 2125
Default Cool CFM 970 1145 1265 1395 1405 1565 1775 1945
Decrease (-10%) Cool CFM 885 1025 1110 1250 1270 1425 1610 1770
SLP98UH110XV60C BLOWER MOTOR WATTS - COOLING
Blower Speed
Options
Motor Watts @ Various External Static Pressures - in. wg.
First Stage Second Stage
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Increase (+10%) Cool CFM
Low 81 113 135 165 200 228 251 280 315 220 254 300 346 385 432 472 511 560 600 610
Medium-Low 119 147 179 210 241 273 309 331 358 345 386 414 475 516 547 594 637 681 714 748
Medium-High 157 191 225 265 304 331 377 405 435 492 536 573 623 666 711 761 804 842 891 918
High 220 254 300 346 385 432 472 511 560 675 699 767 839 876 915 973 1033 1062 1115 1134
Default Cool CFM
Low 60 88 114 137 167 187 219 244 276 163 196 231 266 309 348 388 421 451 489 512
Medium-Low 81 108 147 173 195 231 257 288 326 232 263 314 353 412 445 490 516 557 596 649
Medium-High 122 145 182 215 246 286 306 333 360 372 401 449 498 541 577 643 672 695 744 765
High 163 196 231 266 309 348 388 421 451 497 539 579 646 681 734 773 817 851 904 957
Decrease (-10%) Cool CFM
Low 45 62 96 116 132 153 179 199 227 124 146 189 215 245 279 316 331 373 396 423
Medium-Low 56 85 115 134 159 185 215 251 270 163 195 243 270 314 353 397 414 470 496 535
Medium-High 80 114 141 161 203 230 256 294 318 248 274 324 386 416 470 494 539 583 620 652
High 124 146 189 215 245 279 316 331 373 377 413 457 502 548 583 629 684 705 753 783
The effect of static pressure is included in air volumes shown.
The following control congurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts ring rate based on rst- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 450 cfm.