EasyManua.ls Logo

Lenz Digital plus LS100 - Page 16

Lenz Digital plus LS100
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Accessory Decoder LS 100/110
Programming address and settings through the
programming output of LZ100
Address and other settings of LS100/LS110 are stored in so
called “registers”, abbreviated “R”. These registers can be
imagined as a sort of notepad that can have new entries put on
them again and again. The written entries remain stored even
after the power is turned off.
Assignment of registers
LS100/LS110 has 6 registers, that are used as follows:
Reg
CV
AltC
V
used for allowed range of
values
1 1 513 address 1 - 256
2 3 515 settings output 1 0 - 15; 32; 33 - 47
3 4 516 settings output 2 0 - 15; 32; 33 - 47
4 5 517 settings output 3 0 - 15; 32; 33 - 47
5 6 518 settings output 4 0 - 15; 32; 33 - 47
7 7 519 version number 2.2
8 8 520 manufacturer ID 99
-
29
541 Configuration 128
Table 1: Assignment of registers
The value stored in R1 thus determines the address, the
‘number’ with which the connected function devices are
addressed.
R†2†to†5 behave the same: The values stored here determine
the settings of the outputs. From table 2 you see the values that
need to be entered for a desired setting of an output:
Value Setting
0 - 15 Pulse output, variable
pulse duration
32 Constant output
33 - 47 Flashing, variable rate
Table 2: Settings of the outputs
Values other than the ones listed are not allowed and will lead to
random results.

Related product manuals