62
EDK82MV752 DE/EN/FR 7.2
Commissioning of 8200 motec without function module
l The 8200 motec can only be used when the FIF cover is mounted! (delivery status).
If the FIF cover is not mounted, the 8200 motec is inhibited (keypad: ).
l Since the 8200 motec without a function module does not provide any control termi-
nals, starting and stopping during operation is also possible by switching the mains.
l The function saves the setpoint at the time the operation is interrupted when swit-
ching the mains or in case of mains failures. The drive restarts automatically as soon as
the mains recovers!
l If the drive does not start at step ( is not off), press to enable the 8200 motec.
l The 8200 motec (device variant with digital switching output K1) without function mo-
dule requires an external DC voltage for the operation of this output.
8200mot146
A
L1/L2/L3/PE
W
2
U
2
V
2
U
PE
1
V
1
W
1
w
j
y
0....- 50 Hz
z
0....+50 Hz
z
y
wx
v
t
u
s
5000
cd
j
Hz
0
1
40
3
1
2
AIF
z
y
wx
v
t
u
s
88888
8888
888
8
abcde
j
gfkih PS
mno
p
qr
Hi
Hz
%sh
rpm
°C
W
m
AV
Lo
E82ZBB
E82ZWLxxx
8200mot170
Step Comment
Connect diagnosis terminal (contains
keypad) with motec. Put the plug of
the connecting cable into the AIF in-
terface on the motec.
Diagnosis terminal and connecting cable are not included in the scope of supply.
Connect mains voltage.
Automatic start is possible!
The controller is ready for operation after approx. 1 second.
Keypad: 
Select setpoint via the function.
Activate
))
CW rotation
goes off. The drive is running now.
Display indicates output frequency.
CCW rotation
Faults during commissioning or operation? chapter 7