Installation
4-8 821XKlimaBA0399
4.2.2 Power connections
4.2.2.1 Mains connection
- Connect the mains cables with the screw terminals
L1, L2, L3.
- Tightening torques
Terminals
Type
L1, L2, L3, +UG, -UG PE connection
8211 - 8218 0.5 ... 0.6 Nm (4.4 ... 5.3 lbin) 3.4 Nm(30 lbin)
4.2.2.2 Motor connection
Because of the EMC safety we recommend the use of screened
motor cables only.
- 8211 - 8214: On the front FAST-ON connector.
- 8215 - 8218: On the front metall surface.
- Connect the motor cables to the screw terminals U, V, W
anschließen.
- Observe correct pole connection.
- Tightening torques
Terminals
Type
U, V, W PE connection
Screen/
strain relief
T1, T2
8211 -
8218
0.5 ... 0.6 Nm
(4.4 ... 5.3 lbin)
3.4 Nm
(30 lbin)
- -
- Switching on the motor side of the controller is permitted
- for safety switch off (emergency switch off).
- during operation under load.