10 Parameter reference
10.2 Parameter list | C00994
297
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00994
Parameter | Name:
C00994 - Flying restart fct.: Current
Data type: INTEGER_16
Index: 23581
d
= 5C1D
h
Current to be injected during the flying restart process
•100% ≡ rated motor current (C00081
).
• The flying restart current should amount to 10 ... 25 % of the rated motor current.
Flying restart function
Setting range (min. value | unit | max. value) Lenze setting
0.0 % 100.0 25.0 %
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100